Detail produk:
|
|
Tempat asal: | Cina |
---|---|
Nama merek: | HENGFENGYOU |
Sertifikasi: | ISO IEC CB COC KEMA SNI SABS CCC |
Nomor model: | S11 S13 S15 |
Syarat-syarat pembayaran & pengiriman:
|
|
Kuantitas min Order: | 1 |
Harga: | 200-200000/piece |
Kemasan rincian: | kayu |
Waktu pengiriman: | 15 hari |
Syarat-syarat pembayaran: | LC T / T |
Menyediakan kemampuan: | 5000 Potongan / Tahun |
Informasi Detail |
|||
Pemakaian: | Daya, Trafo Distribusi | Tahap: | Tiga |
---|---|---|---|
frekuensi: | 50 / 60Hz | Tipe: | jenis minyak transformator arus terbenam |
Bahan: | Tembaga + alumnium | Kelompok vektor: | Dyn11 / Yzn11 |
Bahan berliku: | Cooper | ||
Cahaya Tinggi: | transformator distribusi terbenam minyak,transformator daya terbenam minyak |
Deskripsi Produk
330kV Oil Immersed Transformer
Perkenalan produk
330kV oil immersed power transformer is a self-developed product for the transformation of urban and rural power grids in China on the basis of absorbing advanced technologies at home and abroad. Transformator daya terbenam minyak 330kV adalah produk yang dikembangkan sendiri untuk transformasi jaringan listrik perkotaan dan pedesaan di Cina berdasarkan menyerap teknologi canggih di rumah dan di luar negeri. Its performance index is superior to GB/T6451< Technical parameters and requirements of three-phase oil immersed power transformer>, fully in line with manufacturing standards of JB/Y3837-1996 Indeks kinerjanya lebih unggul dari GB / T6451 <Parameter teknis dan persyaratan transformator daya tiga fase minyak>, sepenuhnya sejalan dengan standar produksi JB / Y3837-1996
Fitur struktural
1. Low loss and noise: the core plate adopts the laminating form of high-performance silicon steel sheet and five layer step full oblique joint, which can provide low no-load loss and noise. 1. Kehilangan dan kebisingan rendah: pelat inti mengadopsi bentuk laminasi lembaran baja silikon kinerja tinggi dan lima langkah bersama sambungan miring, yang dapat memberikan kehilangan dan kebisingan tanpa beban yang rendah. The oil tank adopts the technology of magnetic shielding and copper shielding. Tangki minyak mengadopsi teknologi pelindung magnetik dan pelindung tembaga. According to the different positions of the leakage magnetic field, measures are taken to reduce the eddy current loss, which reduces the load loss and fundamentally solves the local overheating of the transformer. Menurut posisi yang berbeda dari medan magnet bocor, langkah-langkah diambil untuk mengurangi kehilangan arus eddy, yang mengurangi kehilangan beban dan secara mendasar menyelesaikan overheating lokal transformator.
2. Safe operation: the partial discharge capacity of the product is kept below 100pC. 2. Pengoperasian yang aman: kapasitas peluahan sebagian produk dijaga di bawah 100pC. In order to prolong the service life of the transformer and improve its short circuit resistance, the cooling structure is designed reasonably. Untuk memperpanjang masa pakai transformator dan meningkatkan resistensi hubung singkatnya, struktur pendingin dirancang secara wajar. When the transformer is short circuited, the mechanical stress of the winding conductor is low, and there are other short-circuit withstand measures and strict production process as guarantee. Ketika trafo dihubung pendek, tekanan mekanis dari konduktor belitan rendah, dan ada tindakan menahan hubung singkat lainnya dan proses produksi yang ketat sebagai jaminan.
3. Reliable operation: at present, oil immersed power transformer usually controls on load operation by limiting the average temperature rise of winding to realize the thermal life of transformer. 3. Operasi yang andal: saat ini, transformator daya terbenam minyak biasanya mengontrol operasi beban dengan membatasi kenaikan suhu rata-rata belitan untuk mewujudkan umur termal transformator. In the development process, the control of hot spot temperature is more important than that of average temperature for large capacity UHV Transformer. Dalam proses pengembangan, kontrol suhu titik panas lebih penting daripada suhu rata-rata untuk Transformer UHV kapasitas besar. For transformers with natural oil circulation, the average temperature rise of oil may meet the requirements, while the temperature rise of hot spot may exceed its limit. Untuk transformer dengan sirkulasi oli alami, kenaikan suhu rata-rata oli dapat memenuhi persyaratan, sementara kenaikan suhu hot spot dapat melebihi batasnya. Therefore, it is necessary to calculate and strictly control the hot spot temperature rise of large capacity transformer. Oleh karena itu, perlu untuk menghitung dan secara ketat mengontrol kenaikan suhu titik panas dari transformator kapasitas besar.
4. Easy installation and maintenance: in order to reduce the workload field installation, all accessories are pre installed before leaving the factory. 4. Instalasi dan pemeliharaan yang mudah: untuk mengurangi instalasi bidang beban kerja, semua aksesori sudah diinstal sebelum meninggalkan pabrik. The secondary cable is laid on the main body of the transformer before leaving the factory and led to the terminal box and control box. Kabel sekunder diletakkan di badan utama trafo sebelum meninggalkan pabrik dan mengarah ke kotak terminal dan kotak kontrol. Most large capacity transformers adopt natural oil circulation and air cooling, and maintain 70% cooling capacity when the fan stopped. Kebanyakan transformator kapasitas besar mengadopsi sirkulasi oli alami dan pendingin udara, dan mempertahankan kapasitas pendinginan 70% ketika kipas berhenti.
catatan: Due to continuous product improvement, the dimensions provided in this sample are for reference only. Karena peningkatan produk terus menerus, dimensi yang disediakan dalam sampel ini hanya untuk referensi. If necessary, our company can design and produce according to user requirements. Jika perlu, perusahaan kami dapat merancang dan memproduksi sesuai dengan kebutuhan pengguna. Please contact the company in time. Silakan hubungi perusahaan tepat waktu.
Kapasitas yang ternilai (kVA)
|
Penyadapan Rentang tegangan tinggi (%) |
LV berliku (kV) |
Vektor Kelompok |
Tanpa beban Kerugian (w) |
Beban Kerugian (w) |
Tanpa beban saat ini (%) |
Impedansi tegangan(%) |
90000 |
345 34 ± 2X2.5% 363 36 ± 2X2.5% |
10.5 13.8 15.75 18 20 |
YNd11 | 68.0 | 274 | 0,44 | 14 ~ 15 |
12000 | 85.0 | 340 | 0,44 | ||||
150000 | 101 | 402 | 0,41 | ||||
180000 | 116 | 461 | 0,38 | ||||
240000 | 145 | 572 | 0,34 | ||||
360000 | 198 | 802 | 0,34 | ||||
370000 | 202 | 818 | 0,30 | ||||
400000 | 214 | 867 | 0,30 | ||||
720000 | 332 | 1347 | 0,20 | ||||
Catatan: jika Anda memiliki persyaratan khusus lainnya, Silakan hubungi: 86-0532-80966388 |
· Instruksi pemesanan:
1. Kebutuhan pelanggan menyediakan parameter utama transformator (tegangan input dan output, kapasitas, kehilangan, dll.)